Home > ATS Test and Tag Insights > How often should a RCD be tested?

How often should a RCD be tested?

AS/NZS 3760:2022 specifies the recommended frequency of testing both Fixed and Portable RCD’s for all states except Queensland.

Sarah Allen
  • Fixed RCD’s in factories, manufacturing, assembly, maintenance, fabrication and other hostile environments are to be push button tested every 6 months and trip time tested by a competent person annually.
  • Fixed RCD’s in non-hostile environments and residential areas of hotels, boarding houses, halls, hostels and accommodation houses are to be push button tested every 6 months and trip time tested by a competent person every 2 years.
  • Portable RCD’s in factories, manufacturing, assembly, maintenance, and fabrication environments are to be push button tested daily or before every use and trip time tested by a competent person annually.
  • Portable RCD’s in other hostile environments are to be push button tested 3 monthly and trip time tested by a competent person annually.
  • Portable RCD’s in non-hostile environments are to be push button tested every 3 months and trip time tested by a competent person every 2 years.
  • Portable RCD’s in residential areas of hotels, boarding houses, halls, hostels and accommodation houses are to be push button tested every 6 months and trip time tested by a competent person every 2 years.

In Queensland the following retest frequencies apply in accordance with QLD Electrical Safety Regulations 2013

For more information on RCD Testing, please click here.