Test and Tag retest frequencies vary by State in Australia.
Below is a convenient summary of the requirements across Australia.
For detailed information you can refer to your State Specific requirements on our web site.
Our friendly team in our national support office are also happy to answer an questions you may have. Feel free to call us on 1300 287 669.
All States excluding QLD align with AS/NZS 3760:2022
Type of Environment and / or Equipment | NSW, ACT, TAS, SA, NT, VIC and WA |
---|---|
Factories, workshops, places of work or repair manufacturing, assembly, maintenance, fabrication | 6 months |
Environment where the equipment or supply flexible cord is subject to flexing in normal use OR is open to abuse OR is in a hostile environment | 12 months |
Environment where the equipment or supply flexible cord is NOT subject to flexing in normal use OR is NOT open to abuse OR is NOT in a hostile environment | 5 years |
Residential type areas of hotels, residential institutions, motels, boarding houses, halls, hostels, accommodation houses and the like | 2 years |
Equipment used for Commercial Cleaning | 6 months |
Hire Equipment | Inspection prior to hire AND 3 monthly Test and Tag |
Queensland aligns with the QLD Electrical Safety Regulations 2013
Class of Work QLD | Queensland |
---|---|
Construction Work in QLD | 3 monthly |
Manufacturing Work in QLD | 6 monthly Single Insulated 12 monthly Double Insulated |
Service Work QLD | Annual OR all circuits protected by RCD and RCD tested regularly |
Office Work QLD | 5 Yearly OR all circuits protected by RCD and RCD tested regularly |
Amusement Work QLD | 6 monthly Single Insulated 12 monthly Double Insulated |
Rural Work QLD | Annual OR all circuits protected by RCD and RCD tested regularly |